Impact of Apartment Tightness on Temperature Variability During a Fire.
Opis bibliograficzny
Szczegóły publikacji
Streszczenia
Along with the thermal modernization process of old residential buildings, there has been a significant increase in the air tightness of apartments, which may contribute to the deterioration of the safety of users and rescue teams in the fire. The main goal of the study was to investigate the impact of air-tightness of apartment on fire growthhistory and temperature variabilitydistribution. In the work, an experimental method was applied. Two full-scale fire tests were carried out, one in a sealed apartment and the other in unsealed one. The temperature was measured by thirty-two thermocouples. Two thermal imaging and video cameras are also used to evaluatedepict a temperature field as well as flame and smoke height. Based on the analysis, conclusions have been formulated. It is noteworthy that the highest temperatures and significant increase in pressure were obtained in a sealed apartment but dangerous and critical conditions firefighters' safety were achieved faster and persisted much longer in an unsealed one.
Linki zewnętrzne
Identyfikatory
Metryki
Eksport cytowania
Wsparcie dla menedżerów bibliografii:
Ta strona wspiera automatyczny import do Zotero, Mendeley i EndNote. Użytkownicy z zainstalowanym rozszerzeniem przeglądarki mogą zapisać tę publikację jednym kliknięciem - ikona pojawi się automatycznie w pasku narzędzi przeglądarki.
Informacje dodatkowe
| Liczba arkuszy wydawniczych: | 200.00 |
|---|---|
| Status: | przed korektą |
| Rekord utworzony: | 6 lipca 2023 23:52 |
| Ostatnia aktualizacja: | 9 września 2025 14:22 |